Operation
7.19 Drive Control Chart (DCC)
SINAMICS DCP
Operating Instructions, 09/2019, A5E34382853K
379
Step 3
After a folder has been selected, STARTER copies the DCB library into this local folder. 2
folders named "OEM" and "USER" are created.
Step 4
Copy the OEM folder to an empty memory card.
Note
The memory card supplied from Siemens as option S03 includes, when supplied, a dump
of the inte
rnal device firmware. These files are only required to update firmware.
These files can be deleted
for all other applications of the memory card. Copy the files
into a local folder of your PG/PC and delete the files on the memory card, before you use
the c
ard for the functions described in this chapter.
Step 5
Insert the CompactFlash Card into the switched-off drive and switch on (POWER ON).
The DCB library is copied into the non-volatile memory (ROM) in the drive during power-
up. The process is complete as soon as the power-up has ended (operating state 7.0
reached).
Step 6
Switch off the device.
The memory card can now be removed if the selected parameterization permits operation
without memory card.
After the SINAMICS DCP has been switched on and has run up the DCC option is ready.
Repeat
steps 5 and 6 on additional SINAMICS DCP devices.
Note
If DCC is installed in the drive, the power
-up time increases by approx. 10 s.
Note
This procedure does not
transfer the STARTER parameter assignments into the unit. In
order to transfer the parameter assignments from STARTER into the drive, the "Load into the
target system" function must be run in STARTER.