Technical specifications
10.2 Device data
SINAMICS DCP
430 Operating Instructions, 09/2019, A5E34382853K
Use Exclusively for cabinet installation
Cooling method Forced ventilation Forced air cooling with integrated fans
The fan speed is changed as a function of the temper-
atures of the power units.
3
Fan noise level dB(A) 65 ... 80 The fan noise changes as a function of the fan speed,
which is controlled dependent on the temperatures of
Power connections
- P1, N1, P2, N2
max. 95 mm²
M8 bolts, 13 Nm
MTBF: Expected operating time between two consecutive failures: 20 years