EasyManua.ls Logo

Siemens sinamics dcp - Page 79

Siemens sinamics dcp
450 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electrical connection
5.6 Additional system components
SINAMICS DCP
Operating Instructions, 09/2019, A5E34382853K
77
X524 electronic power supply
Table 5- 14 Terminals for the X524 electronic power supply
Connector
Terminal
Designation
Technical specifications
+
Electronic power supply
Voltage: 24 VDC (20.4 – 28.8 V)
Power consumption: max. 0.6 A
1)
Max. current via jumper in connector:
20 A (15 A according to UL/CSA)
+
Electronic power supply
M
Electronics ground
M Electronics ground
1)
Including the current consumption for the digital outputs
The maximum cable length that can be connected is 30 m.
Note
The two "+" or "M" terminals are jumpered in the c
onnector. This ensures that the supply
voltage is looped through.
The current consumption increases by the value for the DRIVE
-CLiQ node. The digital
outputs are supplied via terminals X520, X521, and X522.
X520 bidirectional digital inputs/outputs
Table 5- 15 Screw terminal X520
Connector
Terminal
Designation
1)
Technical specifications
1
L1+
See Section
"Technical specifications"
2
DI/DO 0
3
DI/DO 1
4
DI/DO 2
5
DI/DO 3
6
DI/DO 4
7 DI/DO 5
8
DI/DO 6
9
DI/DO 7
10 M1 (GND)
1)
L1+: A 24 V DC power supply for DI/DO 0 to 7 (first potential group) must always be connected if
at least one DI/DO of the potential group is used as an output.
M1: A ground reference for DI/DO 0 to 7 (first potential group) must always be connected if at least
one DI/DO of the potential group is used as either an input or output.
DI/DO: Bidirectional digital input/output