Electrical connection
5.6 Additional system components
SINAMICS DCP
Operating Instructions, 09/2019, A5E34382853K
77
X524 electronic power supply
Table 5- 14 Terminals for the X524 electronic power supply
Voltage: 24 VDC (20.4 – 28.8 V)
Power consumption: max. 0.6 A
1)
Max. current via jumper in connector:
20 A (15 A according to UL/CSA)
M Electronics ground
1)
Including the current consumption for the digital outputs
The maximum cable length that can be connected is 30 m.
Note
The two "+" or "M" terminals are jumpered in the c
onnector. This ensures that the supply
voltage is looped through.
The current consumption increases by the value for the DRIVE
-CLiQ node. The digital
outputs are supplied via terminals X520, X521, and X522.
X520 bidirectional digital inputs/outputs
Table 5- 15 Screw terminal X520
See Section
"Technical specifications"
7 DI/DO 5
10 M1 (GND)
L1+: A 24 V DC power supply for DI/DO 0 to 7 (first potential group) must always be connected if
at least one DI/DO of the potential group is used as an output.
M1: A ground reference for DI/DO 0 to 7 (first potential group) must always be connected if at least
one DI/DO of the potential group is used as either an input or output.
DI/DO: Bidirectional digital input/output