Electrical connection
5.6 Additional system components
SINAMICS DCP
86 Operating Instructions, 09/2019, A5E34382853K
6SL3055-0AA00-3FAx
Unit
Value
Voltage drop, output
(I/O power supply to the output)
V
DC
0.5
Max. total current of outputs (per group)
up to 60° C
up to 50° C
up to 40° C
A
DC
A
DC
A
DC
2
3
4
Response time The response time for the digital inputs/outputs (TM15 DI/DO) con-
sists of the following elements:
• Response time on the component itself
(approx. 1/2 DRIVE-CLiQ clock cycle).
• Transmission time via the DRIVE-CLiQ connection
(approx. 1 DRIVE-CLiQ clock cycle).
• Evaluation on the Control Unit (see function diagram)
For additional information:
SINAMICS DCP List Manual, Chapter "Function block diagrams"
Weight
kg
1.0
Protective conductor connection
On enclosure with M4/1.8 Nm screw
Approvals UL and cULus, http://www.ul.com (www.ul.com)