Motor Modules Booksize Compact as expansion axes
7.8 Technical data
SINAMICS S120 Combi
134 Manual, Edition 07/2012, 6SL3097-4AV00-0BP3
Table 7- 10 Technical data Double Motor Modules Booksize Compact (2 x 1.7 A to 2 x 5 A)
Double Motor Modules Booksize Compact 6SL3420- 2TE11-0AAx 2TE13-0AAx 2TE15-0AAx
Output current
Rated current (I
n
)
Base-load current (I
H
)
Intermittent duty current (I
S6
) 40%
Peak current (I
max
)
A
ACrms
A
A
ACrms
A
ACrms
2 x 1.7
2 x 1.5
2 x 2
2 x 5.1
2 x 3
2 x 2.6
2 x 3.5
2 x 9
2 x 5
2 x 4.3
2 x 6
2 x 15
Output voltage V
ACrms
0 - 0.717 x DC link voltage
DC link current I
d
A
DC
4.1 7.2 12
DC link voltage
(up to 2000 m above sea level)
V
DC
510 – 720
DC link capacitance μF 165 165 165
Overvoltage tripping
Undervoltage tripping
1)
V
DC
V
DC
820 ± 2 %
380 ± 2 %
Electronics power supply V
DC
24 (20.4 - 28.8)
Electronics current consumption at 24 V DC A
DC
1.15 1.15 1.15
Current carrying capacity
DC link busbar
Reinforced DC link busbars
24 V busbar
A
A
A
100
150
20
100
150
20
100
150
20
Max. current motor brake A 2 x 2 2 x 2 2 x 2
Unit rating
Based on I
n
(600 V, 8 kHz)
Based on I
H
kW
kW
2 x 0.9
2 x 0.8
2 x 1.6
2 x 1.4
2 x 2.7
2 x 2.3
Total power loss
(including electronics losses)
2)
at 8 kHz
W 114 134 194
Max. pulse frequency
Without derating
With derating
kHz
kHz
8
16
8
16
8
16
Max. ambient temperature
Without derating
With derating
°C
°C
40
55
Sound pressure level dBA <60 <60 <60
Cooling method Internal air cooling using an integrated fan
Cooling air requirement m
3
/h 29.6 29.6 29.6
Weight kg 3.4 3.4 3.4
1) Default for 400 V line supplies; undervoltage trip threshold can be reduced by a maximum of 80 V and is adjusted to the
parameterized line voltage.
2) For an overview, see the power loss tables in chapter Control cabinet installation