DC link components
8.2 Control Supply Module CSM
SINAMICS S120 Combi
Manual, Edition 07/2012, 6SL3097-4AV00-0BP3
153
8.2.3.2 X1 line connection
Table 8- 7 X1 line connection
Terminal Technical specifications
U1
V1
W1
Supply voltage:
3-ph. 380 V - 480 V AC, 50 / 60 Hz
Max. connectable cross-section: 4 mm
2
Type: Screw terminal 4 (see Chapter "Control cabinet installation and
EMC / connection system")
Tightening torque: 0.5 - 0.6 Nm
PE connection M5 screw / 3 Nm at the housing
8.2.3.3 X21 signaling contact
Table 8- 8 X21 signaling contact
Terminal Technical specifications
1
2
Voltage 24 V DC
max. load current 0.5 A (ohmic load)
Max. connectable cross-section 1.5 mm
2
Type: Screw terminal 2 (see Chapter "Control cabinet installation and EMC / connection system")
The 2-pole terminal connector for the signaling contact is included in the Completion Kit provided.
The signaling contact can be wired to a digital input (DI) of the Control Unit to indicate the
failure of a Control Supply Module.
The signaling contact operates as an isolated NO contact. When the switch is closed, the
Control Supply Module is "OK" and provides the output voltage. The switch opens in the
event of a fault "Not OK" – when the overtemperature condition is still present, after a pre-
warning, wire breakage, short-circuit etc. The Control Supply Module is correspondingly
switched off.