EasyManua.ls Logo

Siemens SINAMICS S120 Combi - X525 Fail-Safe Digital Output

Siemens SINAMICS S120 Combi
298 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Additional system components
10.1 Terminal Module TM54F
SINAMICS S120 Combi
180 Manual, Edition 07/2012, 6SL3097-4AV00-0BP3
10.1.3.9 X525 fail-safe digital output
Table 10- 9 Terminal block X525
Terminal Designation
1)
Technical specifications
1 DI 21 Voltage: -3 V to +30 V DC
Typical current consumption: 3.2 mA at 24 V
Electrical isolation: Reference potential is terminal M1
The digital input is electrically isolated.
Level (incl. ripple)
High level: 15 V to 30 V
Low level: -3 V to +5 V
Input delay:
2)
For "0" → "1": 30 μs (100 Hz)
For "1" to "0": 60 μs (100 Hz)
2 DO 1+

3 DO 1-
F-DO 1
0.5 A
Reference potential is terminal M1
0.5 A
Reference potential is terminal L1+, L2+ or L3+
Output delay:
2)
For "0" → "1": 300 μs
For "1" → "0": 350 µs
Total current consumption of all DOs: 2 A
Max. leakage current: < 0.5 mA
Switching frequency:
For resistive load: Max. 100 Hz
For inductive load: Max. 0.5 Hz
For lamp load: Max. 10 Hz
Maximum lamp load: 5 W
An F-DO comprises two digital outputs and a digital input for the feedback signal
F-DO 1 = terminals 1, 2 and 3
Max. connectable cross-section: 1.5 mm²
Type: Screw terminal 1 (see "Control cabinet installation and EMC/Connection system")
1) DI: digital input; DO: digital output F-DO: Fail-safe digital output
2) Pure hardware delay