Line-side power components
2.4 Line supply connection via residual-current devices
SINAMICS S120 Combi
Manual, Edition 07/2012, 6SL3097-4AV00-0BP3
33
2.4 Line supply connection via residual-current devices
Selectively tripping, AC/DC-sensitive residual-current devices (type B) can be used in
addition to the overcurrent protection devices.
CAUTION
Residual-current devices have to be installed if the line supply conditions in terms of short-
circuit power and loop impedance at the infeed point are not such that the installed
overcurrent protection devices will trip within the prescribed period if a fault occurs. Since
TT line supplies do not generally meet this requirement, residual-current devices must
always be installed for this type of system.
Residual-current operated circuit breakers (RCD)
DANGER
Residual-current operated circuit breakers alone are not permissible to provide protection
against direct and indirect contact.
When using residual-current operated circuit breakers, it should be noted that
It is only permissible to use a delayed tripping, selective AC/DC-sensitive residual-current
operated circuit breaker, type B.
The max. permitted grounding resistance of the "selective protective device" is observed
(83 Ω max. for residual-current devices with 0.3 A rated differential current).
Accessible parts of the Power Drive System and the machine are connected to the
system's protective ground conductor.
The maximum total length of the shielded power cables in the drive line-up (motor cables
incl. line supply cables from the line filter to the connecting terminals of the S120 Combi)
is 175 m.
Only recommended line filters must be used during operation.
Only one residual-current circuit breaker may be connected in series (cascading is not
possible).
Switching elements (line disconnector, contactors) for connecting and disconnecting the
drive line-up have max. 35 ms delay time time between the closing/opening of the
individual main contacts.