Additional system components
10.2 DRIVE-CLiQ Hub Module DMC20
SINAMICS S120 Combi
194 Manual, Edition 07/2012, 6SL3097-4AV00-0BP3
10.2.3.2 X524 Electronics power supply
Table 10- 16 Terminals for the electronics power supply
Terminal Designation Technical specifications
+ Electronics power supply
+ Electronics power supply
M Electronics ground
+
M
M Electronics ground
Voltage: 24 V DC (20.4 V – 28.8 V)
Current consumption: Max. 0.5 A
Max. current via jumper in connector: 20 A
Max. connectable cross-section: 2.5 mm
2
Type: Screw terminal 3 (see Chapter "Control cabinet installation and EMC / connection system")
Note
The two "+" and "M" terminals are jumpered in the connector. This ensures that the supply
voltage is looped through.
The current consumption increases by the value for the DRIVE-CLiQ participants.
10.2.3.3 X500 - X505 DRIVE-CLiQ interfaces
Table 10- 17 X500-X505 DRIVE-CLiQ interfaces
Pin Signal name Technical specifications
1 TXP Transmit data +
2 TXN Transmit data -
3 RXP Receive data +
4 Reserved, do not use
5 Reserved, do not use
6 RXN Receive data -
7 Reserved, do not use
8 Reserved, do not use
A + (24 V) Power supply
B M (0 V) Electronics ground
Connector type RJ45 socket
The blanking covers for the DRIVE-CLiQ interfaces are included in the scope of delivery.
Blanking covers (50 pieces) Order number: 6SL3066-4CA00-0AA0