Additional system components
10.2 DRIVE-CLiQ Hub Module DMC20
SINAMICS S120 Combi
Manual, Edition 07/2012, 6SL3097-4AV00-0BP3
195
Note
Only MOTION-CONNECT DRIVE-CLiQ cables may be used to establish connections.
The maximum length of MOTION-CONNECT 500 is 100 m and for MOTION-CONNECT
800PLUS cables, 75 m.
10.2.3.4 Meaning of the LED on the DMC20
Table 10- 18 Meaning of the LED on the DMC20
LED Color Status Description
- Off Electronics power supply is missing or outside permissible tolerance
range.
Green Continuous light The component is ready for operation and cyclic DRIVE-CLiQ
communication is taking place.
Orange Continuous light DRIVE-CLiQ communication is being established.
Red Continuous light At least one fault is present in this component.
Note:
The LED is activated irrespective of whether the corresponding
messages have been reconfigured.
Green / Red Flashing light
0.5 Hz
Firmware is being downloaded.
Flashing
2 Hz
Firmware download is complete. Wait for POWER ON
READY
Green / Orange
or
Red / Orange
Flashing light Component recognition via LED is activated (p0154).
Note:
Both options depend on the LED status when component recognition is
activated via p0154 = 1.
Cause and rectification of faults
The following reference contains information about the cause of faults and how they can be
rectified:
SINAMICS S120 Function Manual (FH1)
SINAMICS S120 Combi List Manual