Additional system components
10.1 Terminal Module TM54F
SINAMICS S120 Combi
Manual, Edition 07/2012, 6SL3097-4AV00-0BP3
191
10.1.9 Technical data
Table 10- 15 Technical data
6SL3055-0AA00-3BAx Unit Value
Current requirement (X524 at 24 V DC)
without DRIVE-CLiQ supply
mA 160
Current requirement (X514 at 24 V DC)
without digital outputs and sensor power supply
mA 38
Sensor power supply with and without forced dormant error
detection (L1+, L2+, L3+)
• Voltage
• Max. load current per output
V
A
24
0.5
- cable length for the 24 V power supply:
- For longer cable lengths, the "Weidmüller Type No. PU DS
24 16A" surge protector must be used.
m < 30
• Fail-safe digital inputs (F-DI)
(with electrical isolation)
• Fail-safe digital outputs (F-DO)
(with electrical isolation)
• Standard digital inputs
(with electrical isolation)
10
4
4
Fail-safe digital inputs (F-DI) and standard digital inputs
• Voltage
• Low-level (an open digital input is interpreted as "low")
• High level
• Current consumption (at 24 V DC)
• Input delay
1)
- for "0" to "1"
- for "1" to "0"
V
V
V
mA
μs
μs
0 to 30
-3 to +5
15 to 30
>2
approx. 30 (100 Hz)
approx. 60 (100 Hz)
Fail-safe digital outputs (F-DO), continuous short-circuit proof
• Voltage
• Max. load current per digital output
• Output delay
1)
- for "0" to "1"
- for "1" to "0"
V
A
μs
μs
24
0.5
300
350
Power loss W 4.5 at 24 V
PE/ground connection On enclosure with
M4 screw
Weight kg approx. 0.9
1)
Pure hardware delay