EasyManuals Logo

Siemens SIPROTEC 7UM62 User Manual

Siemens SIPROTEC 7UM62
638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #286 background imageLoading...
Page #286 background image
Functions
2.42 Monitoring Functions
SIPROTEC, 7UM62, Manual
C53000-G1176-C149-7, Release date 03.2010
286
This malfunction is reported as „Fail U balance“.
If the 90% stator earth fault protection functions are active, a zero voltage results on voltage asymmetry. If this
causes protection pickup, monitoring is relegated to the background and issues no indication.
Figure 2-134 Voltage symmetry monitoring
Phase Sequences of Current and Voltage
To detect any swapped phase connections in the voltage and current input circuits, the phase sequence of the
phase-to-phase measured voltages and the phase currents is checked by monitoring the sequence of same
polarity zero transitions of the voltages having the same sign.
Direction measurement with cross-polarized voltages, path selection for impedance protection, evaluation of
positive sequence voltages for undervoltage protection and unbalanced load detection all assume a clockwise
phase sequence. The current phase rotation is checked and reported individually for side 1 and side 2.
Phase rotation of measured voltages is checked by verifying the phase sequences of the voltages
U
L1
leads U
L2
leads U
L3
and of the phase currents, in each case
I
L1
leads I
L2
leads I
L3
.
Verification of the voltage phase rotation is performed when each measured voltage is at least
|U
L1
|, |U
L2
|, |U
L3
| > 40 V/3
Verification of the current phase sequence is performed when each measured current is at least
|I
L1
|, |I
L2
|, |I
L3
| > 0.5 I
N
.
For abnormal phase sequences (L1, L3, L2), the indications „Fail Ph. Seq. U“, (No. 176) or
„FailPh.Seq I S1“, (No. 265) are issued for side 1, or the indication „FailPh.Seq I S2“, (No. 266) for
side 2, as well as an OR combination of these indications „Fail Ph. Seq.“, (No. 171)
For applications where a counter-clockwise measured values phase sequence appears, this must be notified
to the device via the parameter 271 PHASE SEQ. or an accordingly allocated binary input. If the phase se-
quence is changed in the relay, phases L2 and L3 internal to the relay are reversed, and the positive and neg-
ative sequence currents are thereby exchanged (see also Section 2.47). The phase-related messages, mal-
function values, and measured values are not affected by this.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7UM62 and is the answer not in the manual?

Siemens SIPROTEC 7UM62 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7UM62
CategoryProtection Device
LanguageEnglish

Related product manuals