EasyManua.ls Logo

Siemens SIPROTEC 7UM62 - 4.5 Unbalanced Load (Negative Sequence) Protection (ANSI 46)

Siemens SIPROTEC 7UM62
638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical Data
4.5 Unbalanced Load (Negative Sequence) Protection (ANSI 46)
SIPROTEC, 7UM62, Manual
C53000-G1176-C149-7, Release date 03.2010
473
4.5 Unbalanced Load (Negative Sequence) Protection (ANSI 46)
Setting Ranges / Increments
Trip Time Characteristics
Times
Dropout Conditions
Tolerances
Influencing Variables for Pickup Values
Admissible unbalanced load I
2 perm.
/I
N
(also alarm stage)
3.0 % to 30.0 % Increments 0.1 %
Unbalanced load tripping stage I
2
>>/I
N
10 % to 200 % Increments 1 %
Delay times T
Alarm
, T
I2>>
0.00 s to 60.00 s
or (ineffective)
Increments 0.01 s
Asymmetry factor FACTOR K 1.0 s to 100.0 s
or (ineffective)
Increments 0.1 s
Cooling time factor T
Cool
0 s to 50,000 s Increments 1 s
see also Figure 4-5
Pickup Times (Stage characteristic)
Dropout Times (Stage characteristic)
approx. 50 ms
approx. 50 ms
Alarm stage I
2 perm.
, Tripping stage I2>> Approx. 0.95
Thermal tripping stage Dropout on undershoot of I
2 perm.
Pickup values I
2 perm.
, I
2
>> 3 % of setting value or 0.3 % unbal. load
Delay Times 1 % or 10 ms
thermal characteristic
Time for 2 I
2
/I
2 perm.
20
5 % of reference (calculated) value +1 % current toler-
ance, or 600 ms
Power supply direct voltage in range 0.8 U
Aux
/U
AuxN
1.15 1 %
Temperature in range 23.00 °F (–5 °C) Θ
amb
131.00 °F (55 °C) 0.5 %/10 K
Frequency in range 0.95 f/f
N
1.05 1%
Harmonics
– Up to 10 % 3rd harmonic
– Up to 10 % 5th harmonic
1%
1%

Table of Contents

Related product manuals