EasyManua.ls Logo

Siemens SIPROTEC 7UM62 - Settings

Siemens SIPROTEC 7UM62
638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions
2.46 Temperature Detection by Thermoboxes
SIPROTEC, 7UM62, Manual
C53000-G1176-C149-7, Release date 03.2010
319
2.46.3 Settings
Addresses which have an appended "A" can only be changed with DIGSI, under Additional Settings.
Addr. Parameter Setting Options Default Setting Comments
9011A RTD 1 TYPE Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Pt 100 Ω RTD 1: Type
9012A RTD 1 LOCATION Oil
Ambient
Winding
Bearing
Other
Winding RTD 1: Location
9013 RTD 1 STAGE 1 -50 .. 250 °C; 100 °C RTD 1: Temperature Stage 1
Pickup
9014 RTD 1 STAGE 1 -58 .. 482 °F; 212 °F RTD 1: Temperature Stage 1
Pickup
9015 RTD 1 STAGE 2 -50 .. 250 °C; 120 °C RTD 1: Temperature Stage 2
Pickup
9016 RTD 1 STAGE 2 -58 .. 482 °F; 248 °F RTD 1: Temperature Stage 2
Pickup
9021A RTD 2 TYPE Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected RTD 2: Type
9022A RTD 2 LOCATION Oil
Ambient
Winding
Bearing
Other
Other RTD 2: Location
9023 RTD 2 STAGE 1 -50 .. 250 °C; 100 °C RTD 2: Temperature Stage 1
Pickup
9024 RTD 2 STAGE 1 -58 .. 482 °F; 212 °F RTD 2: Temperature Stage 1
Pickup
9025 RTD 2 STAGE 2 -50 .. 250 °C; 120 °C RTD 2: Temperature Stage 2
Pickup
9026 RTD 2 STAGE 2 -58 .. 482 °F; 248 °F RTD 2: Temperature Stage 2
Pickup
9031A RTD 3 TYPE Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected RTD 3: Type
9032A RTD 3 LOCATION Oil
Ambient
Winding
Bearing
Other
Other RTD 3: Location
9033 RTD 3 STAGE 1 -50 .. 250 °C; 100 °C RTD 3: Temperature Stage 1
Pickup

Table of Contents