Functions
2.3 Ethernet EN100 Modul
SIPROTEC, 7UM62, Manual
C53000-G1176-C149-7, Release date 03.2010
42
2.3 Ethernet EN100 Modul
2.3.1 Functional Description
An Ethernet EN100 Modul allows to integrate the 7UM62 into 100 Mbit Ethernet communication networks
used by process control and automation systems and running IEC 61850 protocols. This standard provides
consistent inter-relay communication without gateways or protocol converters. This allows open and interoper-
able use of SIPROTEC 4 devices even in heterogeneous environments. In parallel to the process control inte-
gration of the device, this interface can also be used for communication with DIGSI and for inter-relay commu-
nication via GOOSE.
2.3.2 Setting Notes
Interface Selection
No settings are required for operation of the Ethernet system interface module (IEC 61850 Ethernet EN100
Modul). If the device is equipped with such a module (see MLFB), the module is automatically configured to
the interface available for it, namely Port B.
2.3.3 Information List
No. Information Type of In-
formation
Comments
009.0100 Failure Modul IntSP Failure EN100 Modul
009.0101 Fail Ch1 IntSP Failure EN100 Link Channel 1 (Ch1)
009.0102 Fail Ch2 IntSP Failure EN100 Link Channel 2 (Ch2)