EasyManuals Logo

Siemens SIPROTEC 7UM62 User Manual

Siemens SIPROTEC 7UM62
638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #483 background imageLoading...
Page #483 background image
Technical Data
4.11 Reverse Power Protection (ANSI 32R)
SIPROTEC, 7UM62, Manual
C53000-G1176-C149-7, Release date 03.2010
483
4.11 Reverse Power Protection (ANSI 32R)
Setting Ranges / Increments
Times
Dropout Ratios
Tolerances
Influencing Variables for Pickup Values
Reverse power P
reverse
>/S
N
–0.50 % to –30.00 % Increments 0.01 %
Delay times T 0.00 s to 60.00 s
or (ineffective)
Increments 0.01 s
Pickup Times
– Reverse power P
reverse
>
approx. 360 ms at f = 50 Hz
approx. 300 ms at f = 60 Hz
Dropout Times
– Reverse power P
reverse
>
approx. 360 ms at f = 50 Hz
approx. 300 ms at f = 60 Hz
– Reverse power P
reverse
> approx. 0.6
– Reverse power P
reverse
>0.25 % S
N
± 3 % of setting value for Q < 0.5 S
N
(S
N
: Rated apparent power,
Q: Reactive power
– Delay times T 1 % or 10 ms
Power supply direct voltage in range 0.8 U
Aux
/U
AuxN
1.15 1 %
Temperature in range 23.00 °F (–5 °C) Θ
amb
131.00 °F (55 °C) 0.5 % / 10 K
Frequency in range 0.95 f/f
N
1.05 1 %
Harmonics
– Up to 10 % 3rd harmonic
– Up to 10 % 5th harmonic
1 %
1 %

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7UM62 and is the answer not in the manual?

Siemens SIPROTEC 7UM62 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7UM62
CategoryProtection Device
LanguageEnglish

Related product manuals