2.22 Overvoltage Protection (ANSI 59)
SIPROTEC, 7UM62, Manual
C53000-G1176-C149-7, Release date 03.2010
180
2.22.3 Settings
Addresses which have an appended "A" can only be changed with DIGSI, under Additional Settings.
2.22.4 Information List
Addr. Parameter Setting Options Default Setting Comments
4101 OVERVOLTAGE OFF
ON
Block relay
OFF Overvoltage Protection
4102 U> 30.0 .. 170.0 V 115.0 V U> Pickup
4103 T U> 0.00 .. 60.00 sec; 3.00 sec T U> Time Delay
4104 U>> 30.0 .. 170.0 V 130.0 V U>> Pickup
4105 T U>> 0.00 .. 60.00 sec; 0.50 sec T U>> Time Delay
4106A DOUT RATIO 0.90 .. 0.99 0.95 U>, U>> Drop Out Ratio
4107A VALUES U-ph-ph
U-ph-e
U-ph-ph Measurement Values
No. Information Type of In-
formation
Comments
6513 >BLOCK O/V SP >BLOCK overvoltage protection
6516 >BLOCK U> SP >BLOCK overvoltage protection U>
6517 >BLOCK U>> SP >BLOCK overvoltage protection U>>
6565 Overvolt. OFF OUT Overvoltage protection switched OFF
6566 Overvolt. BLK OUT Overvoltage protection is BLOCKED
6567 Overvolt. ACT OUT Overvoltage protection is ACTIVE
6568 U> picked up OUT Overvoltage U> picked up
6570 U> TRIP OUT Overvoltage U> TRIP
6571 U>> picked up OUT Overvoltage U>> picked up
6573 U>> TRIP OUT Overvoltage U>> TRIP