Appendix
A.8 Information List
SIPROTEC, 7UM62, Manual
C53000-G1176-C149-7, Release date 03.2010
593
A.8 Information List
Indications for IEC 60 870-5-103 are always reported ON / OFF if they are subject to general interrogation for
IEC 60 870-5-103. If not, they are reported only as ON.
New user-defined indications or such newly allocated to IEC 60 870-5-103 are set to ON / OFF and subjected
to general interrogation if the information type is not a spontaneous event („.._Ev“). Further information on in-
dications can be found in detail in the SIPROTEC 4 System Description, Order No. E50417-H1100-C151.
In columns „Event Log“, „Trip Log“ and „Ground Fault Log“ the following applies:
UPPER CASE NOTATION “ON/OFF”: definitely set, not allocatable
lower case notation “on/off”: preset, allocatable
*: not preset, allocatable
<blank>: neither preset nor allocatable
In column „Marked in Oscill.Record“ the following applies:
UPPER CASE NOTATION “M”: definitely set, not allocatable
lower case notation “m”: preset, allocatable
*: not preset, allocatable
<blank>: neither preset nor allocatable
No. Description Function Type
of In-
for-
matio
n
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interrogation
- Reset LED (Reset LED) Device IntSP on * * LED BO 70 19 1 No
- Test mode (Test mode) Device IntSP on
off
**LEDBO70211Yes
- Stop data transmission (DataS-
top)
Device IntSP on
off
**LEDBO70201Yes
- Unlock data transmission via BI
(UnlockDT)
Device IntSP *
- >Back Light on (>Light on) Device SP on
off
**LEDBIBO
- Clock Synchronization (Synch-
Clock)
Device IntSP
_Ev
* * * LED BO
- Hardware Test Mode (HWTest-
Mod)
Device IntSP on
off
**LEDBO
- Disturbance CFC (Distur.CFC) Device OUT on
off
* LED BO
- Setting Group A is active
(GroupA act)
Change Group IntSP ON
OFF
**LEDBO70231Yes
- Setting Group B is active
(GroupB act)
Change Group IntSP ON
OFF
**LEDBO70241Yes
- Fault Recording Start (FltRecSta) Osc. Fault Rec. IntSP ON
OFF
**LEDBO
- Control Authority (Cntrl Auth) Cntrl Authority DP on
off
* LED BO 101 85 1 Yes
- Controlmode LOCAL (ModeLO-
CAL)
Cntrl Authority DP on
off
* LED BO 101 86 1 Yes
- Controlmode REMOTE (ModeR-
EMOTE)
Cntrl Authority IntSP on
off
* LED BO