2.34 Rotor Earth Fault Protection R, fn (ANSI 64R)
SIPROTEC, 7UM62, Manual
C53000-G1176-C149-7, Release date 03.2010
244
2.34.3 Settings
2.34.4 Information List
Addr. Parameter Setting Options Default Setting Comments
6001 ROTOR E/F OFF
ON
Block relay
OFF Rotor Earth Fault Protection (R,
fn)
6002 RE< WARN 3.0 .. 30.0 kΩ 10.0 kΩ Pickup Value of Warning Stage
Re<
6003 RE<< TRIP 1.0 .. 5.0 kΩ 2.0 kΩ Pickup Value of Tripping Stage
Re<<
6004 T-WARN-RE< 0.00 .. 60.00 sec; 10.00 sec Time Delay of Warning Stage Re<
6005 T-TRIP-RE<< 0.00 .. 60.00 sec; 0.50 sec Time Delay of Tripping Stage
Re<<
6006 X COUPLING -100 .. 800 Ω 398 Ω Coupling Reactance
6007 R SERIES 0 .. 999 Ω 50 Ω Series Resistance (e.g. Meas.
Brushes)
6008 I RE< 1.0 .. 50.0 mA; 0 2.0 mA Pickup Value of Failure Detection
Ire<
6009 PHI I RE -15.0 .. 15.0 ° 0.0 ° Correction Angle for Ire
No. Information Type of In-
formation
Comments
5383 >BLOCK R/E/F SP >BLOCK rotor earth fault prot. (R,fn)
5391 R/E/F OFF OUT Rotor earth fault prot. (R,fn) swit. OFF
5392 R/E/F BLOCKED OUT Rotor earth fault prot. (R,fn) BLOCKED
5393 R/E/F AKTIVE OUT Rotor earth fault prot. (R,fn) is ACTIVE
5394 R/E/F U< block OUT Rot. earth flt. prot. (R,fn) block by U<
5397 R/E/F warning OUT Rot. earth flt.prot. (R,fn) Re< warning
5398 R/E/F picked up OUT Rot. earth flt.prot. (R,fn) Re<< pick.up
5399 R/E/F TRIP OUT Rotor earth fault prot. (R,fn) Re<< TRIP
5400 Failure R/E/F OUT Failure rotor earth fault prot. (R,fn)