Hydro:Evolved User Manual
October 2022 © 2022 Smartrise Engineering, Inc. All Rights Reserved Page 77
The adjustment range is from: 0 12.75 seconds.
Default = 50 ms
Units of Measure: ms
Safe Drop Delay - Delays the time between deactivating the pump motor and the SAFE output
from the MR board.
The adjustment range is from: 0 12.75 seconds.
Default = 50 ms
Units of Measure: ms
The following procedure describes how to adjust the Run Timers.
Navigate to MAIN MENU | SETUP | RUN TIMERS. See Figure 54.
Adjusting start of run timers or end of run timers?
Figure 79: TIMERS Menu Start Timers or Stop Timers
a. If adjusting start of run timers, from the TIMERS menu, click Start Timers and go to
step 3.
b. If adjusting end of run timers, from the TIMERS menu, click Stop Timers and go to
step 4.
If adjusting SM Pick Delay or Delta Pick Delay, select the timer being adjusted and adjust
the value. Go to step 5.
Figure 80: START TIMERS Menu
If adjusting Pump Off Delay or SAFE Drop Delay, select the timer being adjusted and
adjust the value.
Figure 81: STOP TIMERS Menu
Scroll right and press Save.

Table of Contents

Other manuals for Smartrise HYDRO:EVOLVED

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Smartrise HYDRO:EVOLVED and is the answer not in the manual?

Smartrise HYDRO:EVOLVED Specifications

General IconGeneral
BrandSmartrise
ModelHYDRO:EVOLVED
CategoryController
LanguageEnglish

Related product manuals