October 2022 © 2022 Smartrise Engineering, Inc. All Rights Reserved Page 187
Decrease the slowdown distance up from 3’ 06” to 2’ 09”. Place a car calls in down
direction and see if the car still has longer steady state of leveling to the floor. Repeat
these steps , if the car still has longer steady state of leveling to the floor.
Figure 339: SLOWDOWN DISTANCE DOWN – Adjustment
Continue adding a load to the car and verifying the slowdowns until the car is fully loaded.
18.4.10 TSRD Distance
The TSRD is the safe distance from the top and bottom floor level for a car to stop before it hits
the ring buffer in the up direction and the buffer in the down direction. If the car is traveling for
more than 50 fpm within this distance, a TSRD fault occurs and the car performs an emergency
stop.
The following procedure describes how to set the TSRD Distance from the learned position.
Navigate to MAIN MENU | SETUP | HYDRO. See Figure 60.
From the HYDRO SETUP menu, scroll and select TSRD Distance.
Figure 340: HYDRO SETUP Menu – TSRD Distance
From the TSRD Distance menu, set the distance.
Figure 341: TSRD Distance Menu
18.5 Battery Test Time
The battery test time is the time of day the controller searches for a battery fault signal and
creates an emergency battery fault if the fault occurs for three consecutive days.
The following procedure describes how to set the time the batteries.
Navigate to MAIN MENU | SETUP | HYDRO. See Figure 60.