Sets the time it takes before an idle car is parked. If set
to zero, parking is disabled.
Enables parking with doors open
Disables the controller from going out of service due to
reoccurring faults
Sets the number of faults allowed within a 1-hour
window before the car goes out of service. If the car goes
out of service, it remains out of service until the hour
window elapses.
Specifies how many times the car may attempt to start a
run in automatic operation during a 1-minute window. If
the controller attempts additional runs, the car goes out
of service until the real-time clock increments to the next
minute. Set this parameter to zero to disable the feature.
When set ON, OOS does not flash on the PI when the car
is out of group
Default learned floor values
Default inputs and outputs
Defaults all miscellaneous values
Restore all parameters to factory settings
Set ON to default the FRAM chip. This option is self-
resetting. This clears fault/alarm logs, latched faults,
emergency bits and run counter.