Sets the time the car removes itself from answering hall
calls after failing to take an assigned call while on
attendant service. If either the dispatch timeout or
dispatch offline are set to zero, this feature is disabled. If
only one car is on attendant service, this feature should
be disabled.
Specifies how long to sound the buzzer to alert the
attendant that a hall call was pressed
Sets the number of cars allowed to run during
emergency power operation
Sets the first car selected when on emergency power
and when the auto select input is active
When set ON, if the Emergency Power Pretransfer input
is active, cars stop in a faulted state wherever they are.
When set to OFF, cars instead move to the nearest
landing and go out of service with the door open. This
option is used when the system is wired to use
pretransfer input to delay cars both at the transfer into
and out of emergency power.