to "7" correspond to the respective local output of the MultiFlow.
Setting '0' determines that no output link is used for this output.
•
Input
Determines whether the related output should be linked with an input,
i.e. the status of the external output follows the status of the linked
input. Valid pre-settings in this case are "0, 1 .. 4, 5 .. 6”, where "1" to
"4" corresponds to the respective local input of the MultiFlow. "5" and
"6" are used to address the IO module inputs "IN1" and "IN2" and '0'
determines that no input link is used for this output.
•
Delay time
These parameters are used to determine whether the status of the
external output follows the status of the linked in/output immediately or
with a pre-set delay (0, 0.1.. 10sec).
•
Inversion
Determines whether the status of the linked in/output should be
inverted at the external output.
•
Product dependency
The product dependency of the link is defined by this item. Up to 5
dependencies can be defined. For this purpose it is necessary to
specify the index of the respective product according to the product
list (3.5.x.x) (e.g. heating oil = 11). Selecting “0” deactivates the
product dependency. The product dependency determines whether
the according link is active during each delivery ("0") or only during the
delivery of the defined product. Product dependency only applies to
the delivery process. During the MultiFlow's idle status link control this
parameter is not considered.
Since the outputs assume the default statuses when a connection is
broken, the configuration of product-dependent links should take into
account the fact that the idle status of the corresponding output needs
to correspond to the default idle status.
9.14.3.2
Additional hose path
The parameters required to control an additional hose path are found
under menu item 3.1.6.0.4.x.2. The corresponding configuration is to be
carried out separately for each output.