Commissioning TITANUS MICRO·SENS
®
7 – 16 Data: 01/09 MS_A_07-en-e
?
TITANUS
MICRO · SENS
®
CancelAssume
Smoke level
10
9
8
7
6
5
4
3
2
1
0
D
C
B
A
Amount of aspiration points
Pre selection time
min s
5
10
Start
Measuring active
Training mo de activ e
Transp. time not established
00000
s
50,0
s40,0
s
s
s
30,0
20,0
10,0
E
s60,0
V
12,0
V
13,5
Establish transport time
?
?
?
File Record Settings Device-Selection
(Date Time)
Fault messagesStatus Settings ROOM-IDENT
Receptio n Serial No.
Transport time established Transport time invalid
Blow out time
Intake f an
Blow out fan
First the number of aspiration apertures then the blow through time and
blow through and aspiration ventilator voltage must be entered.
Click on the question mark for help.
? Blow through time help
Blow through time (for blow through ventilator voltage 13.5 V)
During blow through time the smoke is blown backwards out of the pipe.
The blow through time can be selected from the following table
(intermediate values = next largest value):
Pipe Length (m) Time (secs)
10 80
15 97
20 113
25 130
30 147
35 163
40 180
1 second should be added to the blow through time for each pipe bend or
angle.