Projection with SF-400 / SF-650
Number of points
Type
Sensitivity
(% Lt/m)
1 2 3 4 5 6 7 8
0,1 A B B B C C C C
0,2 B B C C C C
0,3 B C C C
DM-TM-10
0,4 B
C C
0,5 C C
0,6 C C
0,7 C
0,8 C
0,9 C
1 C
1,1 C
1,2 C
1,3 C
1,4
1,5
1,6
1,7
1,8
1,9
DM-TM-50
2
without additional pipe accessories
Pipe shape
U
Fan
[V]
1 2 3 4 5 6 7 8
I
9
40 40 40 40
U
9
50 50 50 50 50 50
M
9
50 50 50 50 50 50
Double U
9
50 50 50 50 50 50 50 50
permitted total pipe
length [m]
with detector box and/or VSK
Pipe shape
U
Fan
[V]
1 2 3 4 5 6 7 8
I
9
40 40 40
U
9
50 50 50 50 50 50
M
9
50 50 50 50 50 50
Double U
9
50 50 50 50 50 50 50 50
permitted total pipe
length [m]

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the WAGNER TITANUS and is the answer not in the manual?

WAGNER TITANUS Specifications

General IconGeneral
Power Supply24 V DC
Operating Temperature-20°C to +60°C
Alarm OutputRelay contacts
CertificationVdS, EN 54
Humidity Range10% to 95% (non-condensing)