Pipe Design TITANUS MICRO·SENS
®
4 – 16 Data: 01/09 MS_A_04-en-e
Results: The following modules may optionally be used with the corresponding
settings for class B or A:
z Detection unit DM-TM-10 – with a sensitivity of 0,1 % LT/m to
0,6 % LT/m
z Detection unit DM-TM-50 – with a sensitivity of 0,5 % LT/m to
0,6 % LT/m
Possible system parameters:
z I- pipe system
- 9 V fan voltage, max. 40 m overall pipe length
z U- pipe system
- 9 V fan voltage, max. 50 m overall pipe length
z M- pipe system,
- 9 V fan voltage, max. 50 m overall pipe length
z Double U- pipe system,
- 9 V fan voltage, max. 50 m overall pipe length