Pipe Design TITANUS MICRO·SENS
®
4 – 20 Data: 01/09 MS_A_04-en-e
Aspiration apertures
Number of apertures
per pipe system
1 2 3 4 5
Aspiration aperture
in mmTP4F
5
PT)
A
B
C
D
E
6,8
4,6
5,0
4,0
4,2
4,4
3,4
3,6
3,8
4,0
3,0
3,2
3,4
3,6
3,8
Trigger Thresholds I-Pipe system
Trigger threshold
Number of apertures 2 3 4 5
1 blocked aperture
±30 % ±20 % ±15 % ±10 %
2 blocked apertures {TP5F
6
PT
{
±30 % ±20 %
3 blocked apertures
{ { { {
4 blocked apertures
{ { { {
5 blocked apertures
{ { { {
… is/are recognised when main air flow set x %
Example If the blockage of 2 aspiration apertures out of a total of 5 aspiration
apertures is recognised, then with the help of the diagnosis tool flow
monitoring can be set to ±20 %.
For a project planning according to EN 54-20, the air flow monitoring
has to be adjusted to 20 % in either case.
TP
5
PT Opening diameter of the aspiration reducing film
TP
6
PT { not sensible
INSTRUCTION

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the WAGNER TITANUS and is the answer not in the manual?

WAGNER TITANUS Specifications

General IconGeneral
Power Supply24 V DC
Operating Temperature-20°C to +60°C
Alarm OutputRelay contacts
CertificationVdS, EN 54
Humidity Range10% to 95% (non-condensing)

Related product manuals