5 AC 800F Functional Description
5-24
Prim/Sec LED
The Prim/Sec LED of a not redundant AC 800F can only adopt one of these two
states:
Off Normal operation
Orange Self-test is in progress
In the case of the redundant AC 800F the Prim/Sec LEDs on the Primary and
Secondary have different meanings:
Prim/Sec LED on Primary:
Off No redundancy configured
Green static Synchronous operation, normal state in redundancy mode.
Green flashing Unsynchronized operation, transitional state, occurs when data
are being matched with those of the Secondary.
Orange static Redundancy configured, no Secondary found. Secondary
failed or error occurred during redundant operation.
Red static Error occurred in redundancy mode.
Prim/Sec LED on Secondary:
Off No redundancy configured, or operating system not yet
downloaded to AC 800F
Orange static Synchronized operation.
Orange flashing Synchronization still in progress.
Red static Error occurred in redundancy mode
Operating elements
Reset switch
The Reset switch serves for resetting the AC 800F. A warm start or cold start is
initiated, depending on the system status. The reset switch is recessed and can only
be pressed by using a "tool" (e.g. a ball-point pen or similar). The switch is provided
with a delay circuit to avoid accidental actuation. A cold start of the module is
initiated only when the Reset switch is pressed for more than approx. 4 seconds.
Pressing the switch for a shorter time initiates a warm start.