6.2. Cable requirements
Power, auxiliary and control cables have different requirements.
6.2.1. Power cables
For information on the requirements for power cables, ground cable and
equipotential bonding conductor, see:
Power cable specification (3BHS125090 E01)
Power cables engineering guideline (3BHS542290 E01)
6.2.2. Auxiliary and control cables
For information on the requirements for the auxiliary power cable and the control
cables, see Auxiliary power and control cables guideline (3BHS813742 E01).
6.2.3. Synchronization cables
Synchronization cables are used in drives with an ARU. A shielded, 3-phase cable
without neutral wire is required for the supply voltage of the synchronization
transformer.
NOTICE Risk of false signals!
DO NOT lay control cables parallel to the power supply cables.
If this cannot be avoided, maintain a minimum distance of 30 cm
between the control and power supply cables.
Cross control and power supply cables at an angle of 90°