PREVENTIVE AND CORRECTIVE MAINTENANCE
PRODUCT
ACS6000
DOCUMENT KIND
User manual
DOCUMENT ID.
3BHS212794 E01
REV.
N
LANG.
en
PAGE
263/266
5. Disconnect the water tubes (1) from the air-to-water heat exchanger, unplug
the cables (2) and remove the fastening screws.
Figure 10-30 Air-to-water heat connections
6. Lift the heat exchanger out of the cabinet.
CAUTION! The heat exchanger weighs approximately 16 kg and requires a
minimum overhead clearance of 85 cm.
Figure 10-31 Lift heat exchanger out of EXU cabinet
1) Water tube connections
2) Fastening screw
3) Cable connections
1
1
2
3
3