PREVENTIVE AND CORRECTIVE MAINTENANCE
PRODUCT
ACS6000
DOCUMENT KIND
User manual
DOCUMENT ID.
3BHS212794 E01
REV.
N
LANG.
en
PAGE
249/266
A thermostat inside the cabinet where air-to-air heat exchanger is installed 
controls the internal fans (3 and 5 in Fig. 10-26). The fans are switched on when the 
cabinet temperature exceeds the value set on the thermostat.
The ambient fans (1 and 2 Fig. 10-26) are switched on by the air-to-air heat 
exchanger depending on the permanently measured cabinet temperature.
10.4.16.1. Testing the fan units
To switch the fan units on and off for the test, use the thermostats of the fan units.
Procedure
1. Switch on the auxiliary voltage for the air-to-air heat exchanger.
2. Take note of the setting of the thermostat.
The factory-set value is also stated on the Settings label. The label is attached 
to the inside of the cabinet door.
3. To start a fan or a group of fans, adjust the setting of the thermostat to a low 
value (arrow).
4. Check that the fans run smoothly and if a fan is defective, replace the 
complete fan unit.
5. Adjust the setting of the thermostat to its original value.
Thermostat location Identification Factory-set value
ARU B7501 45 °C
INU B7501 45 °C