PREVENTIVE AND CORRECTIVE MAINTENANCE
PRODUCT
ACS6000
DOCUMENT KIND
User manual
DOCUMENT ID.
3BHS212794 E01
REV.
N
LANG.
en
PAGE
217/266
10.4.2. De-energizing and grounding the drive
The following section describes how to de-energize the drive using the local
operator panel of the drive. If the drive is controlled from remote, follow the
established shutdown procedures.
Procedure
1. Enable the local control mode of the CDP control panel.
2. To stop the motor, press the STOP key.
The motor stops according to the preset stop function. When the motor has
reached zero speed, the drive is in ReadyRun.
3. Press the SUPPLY OFF push button to disconnect the drive from the main
power supply.
The following takes place:
MCB opens.
NOTICE Risk of component damage!
Foreign matter and particularly metallic dust can cause failure and
damage when the drive is energized! Ensure that foreign matter cannot
enter the cabinet.
Close the doors and cover openings completely when work
is discontinued.
Retrieve any foreign matter which accidentally dropped into
the cabinet.
LOC
REM
1 L -> 600.0 rpm 0
StateINU ReadyRun
MOTOR SP 0.00 rpm
POWER 0.0 kW