8.5.3. Parameter settings
8.6. Grounding switch and door locking system
The grounding switch of the CBU is a protection device that enables safe access to
the medium voltage units of the drive.
Figure 8-6 CBU grounding switch in ungrounded (A) and grounded (B)
The switch is electromechanically interlocked with a discharge monitoring circuit
that prevents the switch from closing when the DC-link capacitors are still charged.
NOTICE Risk of component damage!
Running the drive system with incorrect data can result in improper
operation, reduction of control accuracy and damage of equipment!
DO NOT change any parameter if the meaning of the parameter and
the effects of the change are not fully understood.
The parameters are set as required for operation and verified during
commissioning and must NOT be changed afterward
1) White illuminated push button:
DC link is grounded
Lights up to indicate that the drive is grounded and that the
locking bar (see 1 in Fig. 8-7) of each medium voltage unit can
be moved to the unlocked or locked position.
2) Yellow illuminated push button: grounding switch unlocked
Lights up to indicate that the grounding switch can be turned
to the ungrounded or grounded position.
Press the yellow push button to turn the grounding switch to
the desired position.
3) Grounding switch in ungrounded position (A)
4) Grounding switch in grounded position (B): When the switch is
in grounded position, the DC link of the drive is connected to the
ground busbar of the drive.
1
2
3
4
B
A