EasyManua.ls Logo

ABB ACS6080 - Status messages

ABB ACS6080
266 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
OPERATION
PRODUCT
ACS6000
DOCUMENT KIND
User manual
DOCUMENT ID.
3BHS212794 E01
REV.
N
LANG.
en
PAGE
171/266
8.7.2. Output switches
Drives can be equipped with motorized output disconnectors, or motorized or
manually-operated output grounding switches.
The switches for actuating the manual output switches are installed inside the
drive cabinets. The location depends on the configuration of the drive. The
switches are accessible after the DC link has been discharged and the doors have
been opened. The open and closed position of the switches is monitored by the
drive.
Depending on the operating state of the drive and the settings of the parameters
for this function, the drive opens or closes the motorized switches.
8.7.3. Manual output isolation
The manual output isolation (MOI) disconnects the output of the drive from the
motor and creates a visible isolating distance in the supply line to the motor.
For more information, see 10.4.9 Drives with the manual output isolation
(optional) on page 231.
8.8. Status messages
The following section lists the status messages of the main operating states that
the drive passes through when:
Drive is put into operation
Drive is stopped
Fault condition has occurred
The status messages are sent to the higher-level control system and are displayed
on the control panel of the drive. For information on other status messages (eg,
fault status messages), see the status words in Appendix G - Signal and
parameter table.
NOTICE Risk of component damage!
The operator must ensure that the motor does not rotate before the
switch is actuated.

Table of Contents

Related product manuals