10.4.10.2. Installing a phase module
1. Check that the busbars (arrows) of the phase module are lubricated.
NOTE If necessary, apply a thin layer of the supplied electrical
contact grease.
2. Make sure that the disconnected water hoses, fiber optics and power supply
leads are out of the way before pushing the phase module into the cabinet.
3. Place the lifting table in front of the cabinet and adjust it to the required
height.
4. Push the phase module slowly towards the back of the cabinet until the
busbars engage with the connectors at the back of the cabinet.
5. Screw in and tighten the bolts.
6. Pull the locking sleeve of the female half of the water hose coupling back as
far as possible.
7. While holding it in this position, push it over the fixed male half of the
coupling until it stops.
8. Let go of the locking sleeve and firmly push the female part against the male
part until the coupling locks home with a click.
9. Reconnect the optical fibers and power supply leads.
NOTICE DO NOT mix up the cables. The identification on the label must
correspond to its counterpart on the phase module. Verify the correct
connection with the corresponding wiring diagram.
10. Fasten the cables with cable ties.