Figure 6-34 Cable route in COU (1000 mm) bottom cable entry
2. Fasten the cables with cable ties.
6.8.6.3. Connecting the cables
Conductors
If a twisted pair cable is used, leave the unshielded cable ends twisted until they
reach the terminals.
Leave unshielded conductor ends as short as possible (< 50 mm).
Cable shields
1. Connect the shield of serial communications cables to the fieldbus adapter.
2. Connect the individual shields and the overall shield (if present) of encoder
cables to the separate shield grounding point.
IMPORTANT! DO NOT connect the shields to the terminals of the interface.
NOTE – Different-sized ground clamps are supplied.
1) Cable entry bottom
2) Side view
3) Detail
2
3