ELECTRICAL INSTALLATION
PRODUCT
ACS6000
DOCUMENT KIND
User manual
DOCUMENT ID.
3BHS212794 E01
REV.
N
LANG.
en
PAGE
132/266
6.7. Power, ground and equipotential bonding 
conductor cables
Overview
The following sections describe how to prepare and route cables. For a description 
on how to prepare the cable entries, see “6.6 Preparing cable entry systems for 
TEU, ARU and EXU cabinets” on page 128.
See “Appendix C - Mechanical drawings” for information on:
– Project-specific cable entry
– Distance between point of cable entry and terminals or busbars
– Busbar and fastening hole dimensions
– Busbar designations
See “Appendix D - Wiring diagrams” for information on:
– Conventions for cross-reference and device identification
6.7.1. Determining the cable length
1. Determine the required length of a cable between the point of entry and the 
connection point inside the cabinet. 
2. Cut the cable to the required length before connection.
NOTICE Risk of damage or malfunction!
– Waste inside the cabinet can cause damage or malfunction.
– If possible, DO NOT cut cables inside the terminal compartment.
– Retrieve any waste which accidentally dropped into the cabinet.