EasyManua.ls Logo

ABB ACS6080 - ARU Cable Entry Frames with Type 1 Sealing Modules; Figure 6-15 Short Busbar Removal in ARU

ABB ACS6080
266 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ELECTRICAL INSTALLATION
PRODUCT
ACS6000
DOCUMENT KIND
User manual
DOCUMENT ID.
3BHS212794 E01
REV.
N
LANG.
en
PAGE
130/266
6.6.2. ARU cable entry frames with type 1 sealing modules
Depending on the configuration of the drive, ARUs can be equipped with 3 cable
entry frames (size 3) on the cabinet floor.
In order to connect the cables, you need to remove the phase modules (see10.4.10
Removing and installing a phase module on page 240) and, if necessary, the short
busbars as well (6.6.2.0.1 Removing the short busbars on page 130).
6.6.2.0.1 Removing the short busbars
1. Remove the phase module according to 10.4.10 Removing and installing a
phase module on page 240.
2. If necessary, remove the short busbars (boxes) to facilitate entering the
cables.
3. To remove a busbar, unscrew the bottom bracket and the bolts and then move
the busbar downward and away from the cabinet.
Figure 6-15 Short busbar removal in ARU
4. After you have routed the cables, install the busbars in the reverse order of
removal.
1) Short busbar
2) Remove these bolts
3) Bottom bracket
4) 1/2” wrench
5) 17 mm and 19 mm
1
1
1
1
2
2
3
4
5

Table of Contents

Related product manuals