6.6.2. ARU cable entry frames with type 1 sealing modules
Depending on the configuration of the drive, ARUs can be equipped with 3 cable
entry frames (size 3) on the cabinet floor.
In order to connect the cables, you need to remove the phase modules (see “10.4.10
Removing and installing a phase module” on page 240) and, if necessary, the short
busbars as well (“6.6.2.0.1 Removing the short busbars” on page 130).
6.6.2.0.1 Removing the short busbars
1. Remove the phase module according to “10.4.10 Removing and installing a
phase module” on page 240.
2. If necessary, remove the short busbars (boxes) to facilitate entering the
cables.
3. To remove a busbar, unscrew the bottom bracket and the bolts and then move
the busbar downward and away from the cabinet.
Figure 6-15 Short busbar removal in ARU
4. After you have routed the cables, install the busbars in the reverse order of
removal.
1) Short busbar
2) Remove these bolts
3) Bottom bracket
4) 1/2” wrench
5) 17 mm and 19 mm
1
1
2