Figure 6-35 Shield grounding point for encoder cable on NTAC pulse encoder (A) 
and synchronous serial interface (B)
6.8.7. Routing cables in an EXU cabinet
This section applies to a stand-alone EXU. 
6.8.7.1. Auxiliary power and control cables
1. Enter the cables through a free hole of the EMC plate. 
2. On the length of cable that passes through the cable transit, prepare the 
cable according to the following instructions:
– Cable entries with EMC plates: “6.8.4 Preparing cables for EMC plates” 
on page 141
– Cable entries with cable glands: “6.8.3 Preparing cables for cable glands” 
on page 141.
NOTE – Materials for cable fitting, EMC requirements and sealing are not 
supplied for undrilled plates.
1) Terminals
1) Shield grounding point
2) Ground clamp