OPERATION
PRODUCT
ACS6000
DOCUMENT KIND
User manual
DOCUMENT ID.
3BHS212794 E01
REV.
N
LANG.
en
PAGE
177/266
8.9.2. Starting the drive remotely
When the drive system is operated from a higher-level control system or an
operator control desk, follow the instructions in the applicable manuals.
8.9.3. Starting the drive locally
1. Set the CDP control panel to local control mode.
2. If the EMERGENCY-OFF RESET push button on the COU is flashing, press the
push button to cancel flashing.
NOTE – Each time the auxiliary voltage is switched off and on again, the
emergency-off safety relay of the drive is actuated and lets the EMERGENCY-
OFF RESET push button flash. The EMERGENCY-OFF RESET push button also
flashes if the EMERGENCY-OFF push button on the control compartment door,
or any other EMERGENCY-OFF push button linked to the drive, is pressed. If the
EMERGENCY-OFF RESET push button continuous flashing, verify that there is
no emergency-off command active. See “8.10.2 Stopping the drive with the
emergency-off function” on page 181
3. Check that no alarm or fault messages are displayed on the control panel.
• When a fault message is displayed on the control panel, reset the fault.
• If a fault cannot be reset, the responsible personnel must rectify it.
• (Drives with an ARU) When faults are present and the drive is ready, the INU
is “ReadyOn”.
• When alarms and faults are not present and the drive is ready, the INU CDP
control panel displays ReadyOn.
1 L -> 4840.0 V
StateARU ReadyOn
DC VOLT 0.00 V
PRI VOLT 0 V
1 L -> 0.0 rpm
StateINU ReadyOn
DC VOLT 0.00 rpm
PRI VOLT 0 kW