8.10. Stopping the drive
8.10.1. Stopping the drive locally
1. To stop the drive, press the STOP key on the control panel.
The motor stops according to the preset stop function. While the motor stops, 
the status line of the display shows ReadyRef and the run status message 
blinks.
NOTE – During the stop sequence, you can restart the drive by pressing the 
START key.
The drive is now in stopping mode.
2. When the motor has reached zero speed, the drive is “ReadyRun”.
As long as the MCB has not been opened, you can restart the motor at any time.
1 L ->              600.0 rpm    I
StateINU ReadyRef
MOTOR SP  300.00 rpm
POWER 20.0 kW
1 L ->              600.0 rpm   0
StateINU Stopping
MOTOR SP  0.00 rpm
POWER 0.0 kW
1 L ->  0.0 rpm         0
StateINU ReadyRun
MOTOR SP  0.00 rpm
POWER 0.0 kW