OPERATION
PRODUCT
ACS6000
DOCUMENT KIND
User manual
DOCUMENT ID.
3BHS212794 E01
REV.
N
LANG.
en
PAGE
179/266
5. (Drives with an ARU) Press the START key on the ARU control panel:
The ARU starts modulating, the control panel displays “Modulating” and the
status of the ARU changes to Modulating.
When the ARU has reached the status “ReadyRef”, the status of the first INU
and the other INUs change to “ReadyRun”.
6. Enter the reference value.
7. Start the motor with the INU control panels.
After the motor has been magnetized, the motor speed ramps up to the
reference value.
While the motor is magnetizing, the run status message on the display blinks.
When the motor has finished magnetizing, the run status message lights up
permanently.
The drive is now in “ReadyRef” to indicate that the drive system is operating.
1 L -> 0.0 rpm 0
StateINU ReadyRun
MOTOR SP 0.00 rpm
POWER 0.0 kW
1 L -> [600.0 rpm] 0
StateINU ReadyRun
MOTOR SP 0.00 rpm
POWER 0.0 kW
1 L -> 600.0 rpm I
StateINU ReadyRef
MOTOR SP 0.00 rpm
POWER 1000.0 kW