8.10.4. Starting the drive system after an emergency-off
1. To start the drive system after an emergency-off, unlatch the
EMERGENCY-OFF push button.
The EMERGENCY-OFF push button returns to its initial position when turned
into the direction indicated by the arrows on the push button.
2. Press the EMERGENCY-OFF RESET button to reset the emergency-off safety
relay of the drive.
The drive remains in emergency-off state until the DC-link voltage has
dropped to < 50 V (discharged).
After resetting, the status message of the drive changes to ReadyOn.
The status line of the CDP control panel shows the following:
3. The main power supply can be connected to the drive again and the drive
system can be started up.
Alternating display message:
EmergencyOff
EOFF<DCVolt
1 L -> 600.0 rpm
StateINU EmergencyOff
MOTOR SP 0.00 rpm
POWER 0.0 kW

Table of Contents