Parameter Values (Range) Unit Step Default Description
Voltage Mem time 0...3000 ms 1 40 Voltage memory time
Directional mode 1=Non-directional
2=Forward
3=Reverse
2=Forward Directional mode
Characteristic angle -179...180 deg 1 60 Characteristic angle
Pol quantity 1=Self pol
4=Neg. seq. volt.
5=Cross pol
7=Pos. seq. volt.
5=Cross pol Reference quantity used to determine
fault direction
Table 251: FDPHLPDOC Group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Start value Mult 0.8...10.0 0.1 1.0 Multiplier for scaling the start value
Time multiplier 0.05...15.00 0.01 1.00 Time multiplier in IEC/ANSI IDMT curves
Type of reset curve 1=Immediate
2=Def time reset
3=Inverse reset
1=Immediate Selection of reset curve type
Max forward angle 0...90 deg 1 80 Maximum phase angle in forward
direction
Max reverse angle 0...90 deg 1 80 Maximum phase angle in reverse
direction
Min forward angle 0...90 deg 1 80 Minimum phase angle in forward direction
Min reverse angle 0...90 deg 1 80 Minimum phase angle in reverse direction
Table 252: FDPHLPDOC Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation 1=on
5=off
1=on Operation Off / On
Num of start phases 1=1 out of 3
2=2 out of 3
3=3 out of 3
1=1 out of 3 Number of phases required for operate
activation
Curve parameter A 0.0086...120.0000 1 28.2000 Parameter A for customer programmable
curve
Curve parameter B 0.0000...0.7120 1 0.1217 Parameter B for customer programmable
curve
Curve parameter C 0.02...2.00 1 2.00 Parameter C for customer programmable
curve
Curve parameter D 0.46...30.00 1 29.10 Parameter D for customer programmable
curve
Curve parameter E 0.0...1.0 1 1.0 Parameter E for customer programmable
curve
Allow Non Dir 0=False
1=True
0=False Allows prot activation as non-dir when dir
info is invalid
Section 4 1MRS758755 A
Protection functions
244 REC615 and RER615
Technical Manual