Table 253: FDPHLPDOC Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Minimum operate time 40...60000 ms 1 40 Minimum operate time for IDMT curves
Reset delay time 0...60000 ms 1 20 Reset delay time
Measurement mode 1=RMS
2=DFT
3=Peak-to-Peak
2=DFT Selects used measurement mode
Min operate current 0.01...1.00 xIn 0.01 0.01 Minimum operating current
Min operate voltage 0.01...1.00 xUn 0.01 0.01 Minimum operating voltage
Table 254: DPHLPDOC Group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Start value 0.05...5.00 xIn 0.01 0.05 Start value
Start value Mult 0.8...10.0 0.1 1.0 Multiplier for scaling the start value
Time multiplier 0.05...15.00 0.01 1.00 Time multiplier in IEC/ANSI IDMT curves
Operate delay time 40...200000 ms 10 40 Operate delay time
Operating curve type 1=ANSI Ext. inv.
2=ANSI Very inv.
3=ANSI Norm. inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
15=IEC Def. Time Selection of time delay curve type
Directional mode 1=Non-directional
2=Forward
3=Reverse
2=Forward Directional mode
Characteristic angle -179...180 deg 1 60 Characteristic angle
Max forward angle 0...90 deg 1 80 Maximum phase angle in forward
direction
Max reverse angle 0...90 deg 1 80 Maximum phase angle in reverse
direction
Min forward angle 0...90 deg 1 80 Minimum phase angle in forward direction
Min reverse angle 0...90 deg 1 80 Minimum phase angle in reverse direction
1MRS758755 A Section 4
Protection functions
REC615 and RER615 245
Technical Manual