104 Rockwell Automation Publication 6000-TD004D-EN-P - November 2017
Chapter 2 Parameter Descriptions
Power Cell Bypass Upper Limit For Bypassed Feedback Time
Linear Number: P043
Default Value: 100 ms
Minimum Value: 30 ms
Maximum Value: 500 ms
Access Level: R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the Power Cell Bypass Upper Limit For Bypassed Feedback
Time.
Power Cell Bypass Fault Simulation Power Cell Count
Linear Number: P044
Default Value: 0
Minimum Value: 0
Maximum Value: 3
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the power cell count for power cell bypass fault simulation.
Power Cell Bypass Upper Limit Time For Over Temperature
Linear Number: P057
Default Value: 10 s
Minimum Value: 0 s
Maximum Value: 32767 s
Access Level: R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the Power Cell Bypass Upper Limit Time For Over
Te m p e r a t ur e .
Power Cell Bypass Phase A Cell Number For Simulation
Linear Number: P058
Default Value: 0
Minimum Value: 0
Maximum Value: 9
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the Power Cell Bypass Phase A Cell Number For Simulation.
Set this parameter greater than zero when simulating a cell fault.