Rockwell Automation Publication 6000-TD004D-EN-P - November 2017 105
Parameter Descriptions Chapter 2
Power Cell Bypass Phase B Cell Number For Simulation
Linear Number: P059
Default Value: 0
Minimum Value: 0
Maximum Value: 18
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the Power Cell Bypass Phase B Cell Number For Simulation.
Set this parameter greater than zero when simulating a cell fault.
Power Cell Bypass Phase C Cell Number For Simulation
Linear Number: P060
Default Value: 0
Minimum Value: 0
Maximum Value: 27
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the Power Cell Bypass Phase C Cell Number For Simulation.
Set this parameter greater than zero when simulating a cell fault.
Power Cell Bypass Fault Simulation
Linear Number: P061
Default Value: 0
Minimum Value: -32768
Maximum Value: 32767
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the Power Cell Bypass Fault Simulation.
Power Cell Bypass Enable Frequency Range Lower Limit
Linear Number: P065
Default Value: 0.00%
Minimum Value: 0.00%
Maximum Value: 19.99%
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the lower limit for Power Cell Bypass Enable Frequency
Range.