110 Rockwell Automation Publication 6000-TD004D-EN-P - November 2017
Chapter 2 Parameter Descriptions
Current Limitation Heating Time
Linear Number: P442
Default Value: 60 s
Minimum Value: 0 s
Maximum Value: 16384 s
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the Current Limitation maximum overload duration.
Current Limitation Cooling Time
Linear Number: P443
Default Value: 540 s
Minimum Value: 0 s
Maximum Value: 16384 s
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the Current Limitation minimum cooling time.
Current Limitation Decel Ramp Slope Change
Linear Number: P444
Default Value: 120.00%
Minimum Value: 0%
Maximum Value: 399.99%
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the drive maximum overload allowed for a short time.
Current Limitation Cycle Load Control Enable
Linear Number: P445
Default Value: 0
Minimum Value: 0
Maximum Value: 1
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter is used to enable or disable the Current Limitation Cycle Load
Control function.
Value Description
0 Disable Current Limitations Cycle Load Control
1 Enable Current Limitation Cycle Load Control