Chapter 2 Parameter Descriptions
Power Cell DC Bus Rated Voltage
Linear Number: P011
Default Value: 650V (2.3 kV/2.4 kV),
848V (4.0 kV/4.16 kV),
920V (3.0 kV/3.3 kV/6.3 kV/6.6 kV),
976V (6.0 kV/6.9 kV/10.0 kV/11.0 kV)
Minimum Value: 50V
Maximum Value: 1300V
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Offline only
This parameter is the power cell DC bus rated voltage. The value is equal to the
transformer secondary rated line voltage (rms) * 1.414.
Motor Rated Voltage
Linear Number: P012
Default Value: 10000V
Minimum Value: 0V
Maximum Value: 32767V
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Offline only
This parameter is the motor rated line voltage RMS value.
Motor Rated Power
Linear Number: P013
Default Value: 0 kW
Minimum Value: 0 kW
Maximum Value: 32767 kW
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Offline only
This parameter is the motor rated power.
Motor Rated Speed
Linear Number: P014
Default Value: 1500 RPM
Minimum Value: 0 RPM
Maximum Value: 5000 RPM
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Offline only
This parameter is the motor rated speed.

Table of Contents

Other manuals for Allen-Bradley PowerFlex 6000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex 6000 and is the answer not in the manual?

Allen-Bradley PowerFlex 6000 Specifications

General IconGeneral
BrandAllen-Bradley
ModelPowerFlex 6000
CategoryDC Drives
LanguageEnglish

Related product manuals